Energy generation and electrical engineering

THE ANALYSIS OF OPERATING MODE OF CURRENT TRANSFORMER WITH OPEN SECONDARY CIRCUIT BY THE METHODS OF ANALYTICAL CALCULATIONS

Authors

A. V. Zhurakhivskyi
Lviv Polytechnic National University ROR
Yu. A. Kens
Lviv Polytechnic National University ROR
R. Ya. Ferensovych
Lviv Polytechnic National University ROR

Keywords

current transformer secondary circuit overvoltage methods of analytical calculations

Abstract

There has been carried out the analysis of operating modes of current transformers with opening of their secondary circuits. The methods of analytical calculations of voltage levels on the open terminals of secondary windings of current transformers are proposed for using with the purpose of quick analysis of such operating modes. The comparative analysis of calculation results of amplitudes of voltage pulses on the open secondary winding terminals of current transformer type TLM-10, which have been obtained by using computer simulation of its emergency operating mode and analytical calculation, is carried out.

568 1982

How to Cite

[1]
“THE ANALYSIS OF OPERATING MODE OF CURRENT TRANSFORMER WITH OPEN SECONDARY CIRCUIT BY THE METHODS OF ANALYTICAL CALCULATIONS”, Вісник ВПІ, no. 6, pp. 89–94, Feb. 2016, Accessed: Oct. 13, 2026. Available: https://visnyk.vntu.edu.ua/index.php/visnyk/article/view/1856

Author Biographies

A. V. Zhurakhivskyi, Lviv Polytechnic National University
Dr. Sc. (Eng.), Professor, Professor of the Chair of Electrical Systems and Networks
Yu. A. Kens, Lviv Polytechnic National University
Cand. Sc. (Eng.), Assistant Professor
R. Ya. Ferensovych, Lviv Polytechnic National University
Post-Graduate Student of the Chair of Electrical Systems and Networks

Most read articles by the same author(s)