Improvement of the System for Suppressing Ferroresonant Processes in 10 kV Electrical Grids

Authors

  • Z. M. Bakhor Lviv Polytechnic National University
  • A. Ya. Yatseiko Lviv Polytechnic National University

Keywords:

ferroresonant process, electrical network with isolated neutral, voltage transformer

Abstract

Ferroresonant processes (FRP) in 10 kV electrical grids with isolated neutral are considered. These processes occur between the network’s capacitance to ground and the nonlinear inductance of the grounded primary windings of voltage transformers (VT) at the moment of eliminating a single-phase earth fault in the network. In most cases, FRPs in electrical networks are self-extinguishing within several cycles of the power frequency. However, under certain ratios of the network’s capacitive earth-fault current and the voltage transformer parameters, the FRP can become stable (long-lasting) and cause thermal damage to the primary windings of VTs and other electrical equipment.

The duration of such FRPs is limited by the operation time of the devices designed to prevent (suppress) them, or, in their absence, by the time until VT damage occurs or the network configuration changes. To suppress stable FRPs and protect VTs from damage, protection devices are used, their action is directed on the connection of a damping resisting to the open-delta winding of the VT. This principle has been implemented, in particular, in PZF-type protection devices, which have been in operation in 10–35 kV electrical grids for more than 25 years. Over the years of PZF operation, cases of ineffective suppression of FRPs in networks have been recorded. Such events occurred due to changes in the network configuration and, accordingly, the number of operating VTs equipped with PZF devices.

FRPs were studied in 10 kV radial electrical grids with different numbers of operating VTs, and the ranges of capacitive earth-fault currents at which FRPs are stable were determined. It has been established that each number of VTs in 10 kV networks corresponds to its own range of capacitive earth-fault currents. As the number of VTs in the grid increases, the ranges of capacitive earth-fault currents at which stable FRPs occur also expand.

Method for suppressing stable FRPs in 10 kV electrical grids has been proposed, and its effectiveness has been investigated in grids with the isolated neutral. The essence of the method is based on the short-term connection of an active resistor to the neutral of a power transformer. The proposed method for suppressing stable FRPs in 10 kV isolated-neutral electrical networks, as the studies have shown, is effective regardless of the number and type of VTs in the network, as well as regardless of whether FRP suppression devices are installed or absent. Based on the results of the study, the optimal resistance value was determined, the connection of which to the neutral of the power transformer leads to the suppression of stable FRPs. Principle for the technical implementation of the developed “power transformer neutral–resistor” method has been developed.

Author Biographies

Z. M. Bakhor, Lviv Polytechnic National University

Cand. Sc. (Eng.), Associate Professor, Associate Professor of the Chair of Electric Power Engineering and Control Systems

A. Ya. Yatseiko, Lviv Polytechnic National University

Cand. Sc. (Eng.), Associate Professor, Associate Professor of the Chair of Electric Power Engineering and Control Systems

References

“Resonance and Ferroresonance in Power Networks,” CIGRE Technical Report 569, 2014 [Electronic resource]. Available: https://www.scribd.com/document/513700815/ELT-272-9 .

H. Radmanesh, and Hamid F. Seyed, “Analyzing Ferroresonance Phenomena in Power Transformers Including Zinc Oxide Arrester and Neutral Resistance Effect,” Applied Computational Intelligence and Soft Computing, 2012. https://doi.org/10.1155/2012/525494 .

R. Martínez, M. Manana, et al., “Ferroresonance Phenomena in Medium-Voltage Isolated-Neutral Grids: A Case Study,” IET Renewable Power Generation, 2018. https://doi.org/10.1049/iet-rpg.2018.5231 .

M. Kutija, and L. Pravica, “Effect of Harmonics on Ferroresonance in Low Voltage Power Factor Correction System—A Case Study,” Appl. Sci., no. 11, pp. 4322, 2021. https://doi.org/10.3390/app11104322 .

А. В. Журахівський, З. М. Бахор, О. І. Ганус, П. П. Говоров, і А. Я. Яцейко, Ферорезонансні процеси та захист трансформаторів напруги в електричних мережах 6-35 кВ, моногр. Львів, Україна: Вид-во Львівської політехніки, 2019, 324 c.

K. Solak, W. Rebizant, and M. Kereit, “Detection of Ferroresonance Oscillations in Medium Voltage Networks,” Energies, 2020. https://doi.org/10.3390/en13164129 .

Z. Bakhov, A. Yatseiko, and R. Ferensovych, “Assessment of Ferroresonance Processes in Schemes of 6–35 kV Electrical Grids on the Basis of Reliability Analysis,” Energy Engineering and Control Systems. 2020. https://doi.org/10.23939/jeecs2020.02.137.

А. В. Журахівський, Ю. А. Кенс, А. Я. Яцейко, і Р. Я. Масляк, «Ферорезонансні процеси на частоті мережі та пристрої захисту від них,» Вісник Національного університету «Львівська політехніка», № 834, с. 6-13, 2015.

W. Kraszewski, and P. Syrek, “Methods of Ferroresonance Mitigation in Voltage Transformers,” Energies. 2022. https://doi.org/10.3390/en15249516 .

А. В. Журахівський, Ю. А. Кенс, А. Я. Яцейко, і Р. Я. Масляк, «Захист електричних мереж 6–35 кВ від ферорезонансних процесів,» Технічна електродинаміка, № 5, с. 70-76, 2013.

ABB. VT Guard Pro, solution for ferroresonance elimination. Zurich: ABB, 2020. [Electronic resource]. Available: https://new.abb.com/medium-voltage/apparatus/instrument-transformers-and-sensors-id/products/iec-indoor-voltage-transformers/ferroresonance-elimintation-vt-guard-pro.

KMB Systems. AFR 31 Smart Load – Active Load for Elimination of Ferroresonance. Brno: KMB Systems, 2019. – [Electronic resource]. Available: https://www.kbh.cz/eu/p/afr-31 .

ElektroAtlas. Ferro-Damp voltage transformer protection device against ferroresonance. Kyiv: ElektroAtlas, 2021. [Electronic resource]. Available: https://elektroatlas.com.ua/power-equipment-en/devices-for-network-protection-en/ferro-damp-tool-df-1-en-1 .

О. М. Равлик, і Н. О. Равлик, «Програмний комплекс «REC» для аналізу процесів в електричних мережах, системах їх захисту й автоматики,» Свідоцтво про реєстр. авт. права на твір, № 62351, 2015.

Abstract views: 2

Published

2026-02-07

How to Cite

[1]
Z. M. Bakhor and A. Y. Yatseiko, “Improvement of the System for Suppressing Ferroresonant Processes in 10 kV Electrical Grids”, Вісник ВПІ, no. 6, pp. 60–65, Feb. 2026.

Issue

Section

ENERGY GENERATION, ELECTRIC ENGINEERING AND ELECTROMECHANICS

Metrics

Downloads

Download data is not yet available.