Evaluation of the Oscillating Power in Asymmetrical Non-Sinusoidal Modes of Electric Networks

Authors

  • M. Y. Burbelo Vinnytsia National Technical University
  • O. V. Stepura ITC "Energy Accounting" Ltd., Vinnytsia

DOI:

https://doi.org/10.31649/1997-9266-2019-142-1-24-30

Keywords:

electrical networks, asymmetric nonsinusoidal mode, distortion source detection

Abstract

The possibility of detection and evaluation of the influence of distortion sources (asymmetry and higher harmonics) on the quality of electricity of three-phase networks using instantaneous conditional capacities of the reverse and zero sequences is analyzed. Such sources are nonlinear consumers, whose share in total load increases year by year. Nonlinear consumers consume active power at the main frequency and at the same time generate power to the higher harmonics in the network. Significantly in low voltage networks, there is also a share of consumers with asymmetric load of phases. On the basis of the theory of instantaneous power, instantaneous values are allocated on the basis of which informative values can be formed that allow characterizing the influence of nonlinear and asymmetric consumers on deterioration of the quality of electricity, as well as assessing the inefficiency of the distribution network of the electricity supplying organization.

To evaluate the impact of nonlinear and asymmetric consumers, it is expedient to use instantaneous conditional capacities  and , which are essentially the product of instantaneous direct current voltage on the current of the reverse and zero sequence, and to assess the fault of the electricity supply organization, which consists in the ineffective construction of the distribution network — instant conditional capacities  and , which is essentially a product of instantaneous current of direct sequence on the back and zero sequence voltage. The formation of these values is carried out using the system of α, β, 0-coordinates, which greatly simplifies the construction of measuring devices.

In the presence of harmonic distortions, the RMS values of conditional capacities  and  grow and make up from one to ten percent relatively to the main power generated by the voltage and current of the main frequency of the direct sequence. In the case of load asymmetry, the average values of these quantities increase. At the same time an increase  and testifies to the lack of power of power transformers and the inappropriate use of transformers with the scheme of winding connection "star / star with zero sequence" for powering nonlinear consumers.

Author Biographies

M. Y. Burbelo, Vinnytsia National Technical University

Dr. Sc. (Eng.), Professor, Head of the Chair of Electrical Systems of Power Consumption and Energy Management

O. V. Stepura, ITC "Energy Accounting" Ltd., Vinnytsia

 Head

References

Ф. А. Зыкин, «Энергетические процессы в системах электроснабжения с нагрузками, ухудшающими качество электроэнергии,» Электричество, № 12, с. 5-9, 1987.

Ф. А. Зыкин, «Определение степени участия нагрузок в снижении качества электроэнергии,» Электричество, № 11, с. 13-19, 1992.

В. Я. Майер, и Зения «Методика определения долевых вкладов потребителя и энергоснабжающей организации в ухудшении качества электроэнергии,» Электричество, № 9, с. 19-24, 1994.

CIGRE 36.05/CIRED 2 Joint WG CC02 (Voltage Quality). “Review of methods for measurement and evaluation of the harmonic emission level from an individual distorting load,” 1999.

С. С. Смирнов, «Вклад потребителя в уровни напряжения высших гармоник в узлах электрической сети,» Электричество, № 1, с. 56-64, 1996.

Г. Сендерович, «Визначення часткової участі суб’єктів у порушенні якості електричної енергії.» автореферат дис. докт. техн. наук, Донецьк, 2012.

О. Гриб, Г. Сендерович, П. Щербакова, «Науково-технічні аспекти визначення відповідальності за порушення якості електричної енергії,» Стандартизація сертифікація якість, № 6, с. 48-55, 2013.

О. Г. Гриб, Г. А. Сендерович, П. Г. Щербакова, «Особливості визначення часткового вкладу споживача у відповідальність за порушення синусоїдності кривої напруги,» Вісник Вінницького політехнічного інституту, № 1, с. 98-101, 2014.

H. Akagi, E. H. Watanabe, M. Aredes., “Instantaneous power theory and applications to power conditioning,” IEEE Press, Willy-Interscience, p. 379, 2007.

М. Й. Бурбело, С. М. Мельничук, «Визначення потужностей за несиметричних режимів трифазних мереж із заземленою нейтраллю,» Технічна електродинаміка, № 4, с. 71-75, 2015.

Downloads

Abstract views: 342

Published

2019-02-28

How to Cite

[1]
M. Y. Burbelo and O. V. Stepura, “Evaluation of the Oscillating Power in Asymmetrical Non-Sinusoidal Modes of Electric Networks”, Вісник ВПІ, no. 1, pp. 24–30, Feb. 2019.

Issue

Section

ENERGY GENERATION, ELECTRIC ENGINEERING AND ELECTROMECHANICS

Metrics

Downloads

Download data is not yet available.

Most read articles by the same author(s)

1 2 3 > >> 

Similar Articles

You may also start an advanced similarity search for this article.